Inside outside

2. Service space

3. Air-control layer

4. Frame + insulation

5. Sheathing

6. Water-control layer

7. Drainage / battens

8. Outer covering

The supplied poster repeats two labels. Its thirteen numbers are transcribed in the reading guide; they are not thirteen validated construction stages.

Argentina · United States · European Union

2. Draw one continuous line for each control function

On a section through wall, roof, floor and opening, draw an uninterrupted air-control line and a separate water-control line. Mark every seam, corner, penetration and change of material. The Building America air-barrier guidance emphasises continuous connections and sealed penetrations, with the air-control layer aligned with insulation. The teaching section here applies that principle to a faceted enclosure. It is not a tested proprietary dome assembly. [E4]

3. Make a junction sample

Build a small unoccupied sample containing two adjacent panels and part of an opening, using the proposed product system. Label the inside and outside. Demonstrate how the specified tapes, gaskets or membranes join at the corner, where a fastener penetrates and where water leaves the sill. Photograph each stage before the next layer covers it. Use the manufacturer’s permitted primer, substrate condition, overlap and curing instructions. A sample confirms workmanship and compatibility questions; it does not replace the assembly’s design review.

4. Inspect before concealment

The inspection record needs the product labels, batch details where relevant, dry and clean substrate confirmation, corner photographs, penetration list, opening seals and repairs. Keep an access drawing for hidden service connections. An insulation panel with an unsealed edge may look complete from the room while air bypasses it. Do not cover a failed joint simply because the finish layer fits.

5. Read condensation as a physical event

Warm moist air reaching a sufficiently cold surface can deposit water. Roof condensation depends on indoor humidity, air leakage, temperatures and the assembly’s drying ability. Building America’s cold-weather guidance treats these as connected factors. A larger fan is not an automatic repair for a badly located vapour-control layer or an unsealed roof penetration. Record the suspected moisture route before choosing the intervention. [E5]

Insulation assembly: the printed labels and their limits

LabelRetained descriptionSpecification still required
1Pine frameStructural grade and actual species
2Geodesic structureFrame system and joints
3Mineral wool, 80 mmProduct, fit and thermal specification
4Exterior OSB, 18 mmGrade, fastening and moisture exposure
5 / 6Cork-based waterproofing, repeatedOne layer or distinct products?
7Glass-fibre anti-vapour mat, as printedActual product and vapour resistance
8 / 9Sprayed cork finish, repeatedProduct and intended side
10OSB floor, 15 mmSupport spacing and load design
11XPS insulation, 40 mmCompression, fire and moisture requirements
12Vapour barrierProduct and climate-specific position
13Vinyl parquet / floor finishUnderlay, substrate and indoor use
Units and terms in this account

OSB Oriented strand board · XPS Extruded polystyrene · mm millimetre, 0.001 metre