Amager Bakke / CopenHill, Copenhagen. Supplied ZeusC sheet 024. Steel fabrication and survey material matches Johannes Hauptenbuchner’s Züblin Stahlbau presentation of 12 November 2015. Architecture: BIG (Bjarke Ingels Group). [RB-STEELSURVEY]
A three-dimensional survey compares the fabricated plate edges, connection planes and boreholes with the digital model. Hauptenbuchner’s presentation shows those checks before large steel assemblies are erected. The measurements are imported into TEKLA, the model software named in the source. The waste-bunker chord is preassembled to account for welding shrinkage.
| Source label | Readable meaning |
|---|---|
| 3D survey | Three-dimensional measurement of fabricated geometry. |
| Check of planes | Comparison of a connection face with its intended plane. |
| Check of boreholes | Position check of holes at the connections. |
| Soll / Ist | Specified / measured value. |
| Tol / Abw | Tolerance / deviation. |
| i.O. / n.i.O. | In Ordnung / nicht in Ordnung: within / outside the stated acceptance condition. |
| Außerh. Tol | Outside tolerance. |
Plane deviations visible in the contractor’s report
| Plane | Standard deviation | Minimum/maximum deviation | Displayed limit |
|---|---|---|---|
| 1 | 0.617 | 1.322 | ±1.000 |
| 2 | 0.535 | 1.148 | ±1.000 |
| 3 | 0.025 | 0.056 | ±1.000 |
Read the illustration’s labels
CopenHill: compare the three recorded plane deviations
Reported values from slide 12
Standard deviation
Reported extreme
0
0.25
0.5
0.75
1
1.25
1.5
Limit: 1.000
Plane 1
0.617
1.322
Plane 2
0.535
1.148
Plane 3
0.025
0.056
The source does not state the length unit in this excerpt. None is assigned here.
The limit applies to the recorded check; this chart does not certify the whole structure.
These values transcribe slide 12. Plane 1 and plane 2 have maximum deviations beyond the displayed limit; plane 3 does not. The clipped survey output does not state its length unit, so none is assigned here. Borehole codes such as BL1 are identifiers. The complete presentation is linked in the source record; it is a historical project report, not a tolerance specification for a new structure.
Units and terms in this account
BIG Bjarke Ingels Group, the architectural practice
± plus or minus; stated tolerance or uncertainty